Fulham FHS2-UNV-36L

Fulham FHS2-UNV-36L Notlicht-LED-Treiber – Benutzerhandbuch

1. Einleitung

This manual provides essential instructions for the safe installation, operation, and maintenance of the Fulham FHS2-UNV-36L Emergency LED Driver. This device is designed to provide emergency power to LED luminaires in the event of a normal power failure, ensuring illumination for a specified duration. Please read this manual thoroughly before installation or use and retain it for future reference.

2. Sicherheitshinweise

WARNUNG: To reduce the risk of death, personal injury, or property damage from fire, electric shock, falling parts, cuts, abrasions, and other hazards, read all warnings and instructions included with and on the fixture box and all fixture labels. All electrical work must be performed by a qualified electrician in accordance with all applicable national and local electrical codes.

  • Vor der Installation oder Wartung die Stromzufuhr an der Sicherung oder dem Leitungsschutzschalter unterbrechen.
  • Stellen Sie sicher, dass die Eingangslautstärketage to the emergency driver matches the specified range (100-277V AC).
  • Nicht in der Nähe von Gas- oder Elektroheizungen installieren.
  • Verwenden Sie dieses Gerät nur für den vorgesehenen Zweck.
  • This product is designed for use with specific LED loads. Refer to specifications for compatibility.
  • The emergency driver requires a separate battery backup unit (not included) for emergency operation. Ensure the battery unit is compatible and correctly installed.
Label on Fulham Emergency LED Driver showing electrical ratings and warnings.
Abbildung 2.1: Product label displaying electrical ratings and important safety warnings. This label emphasizes the need to consult the instruction manual for complete installation, operating, and maintenance procedures before AC power is supplied to the unit.

3. Produktüberschreitungview

The Fulham FHS2-UNV-36L is an emergency LED driver designed to convert standard LED luminaires into emergency lighting fixtures. It provides constant power output to the LED load during a power outage, ensuring continuous illumination for a minimum of 90 minutes. This unit operates with a universal input voltage range and is suitable for various commercial and industrial applications.

  • Modell: FHS2-UNV-36L
  • Funktion: Notfall-LED-Treiber
  • Notfall Dauer: Mindestens 90 Minuten
  • Eingangslautstärketage: 100-277V AC
  • Ausgangsvolumentage: 11-36V DC
  • Maximale Ausgangsleistung: 20 Watt
  • Batterie-Backup: Not included (requires external battery pack)
Fulham FHS2-UNV-36L Emergency LED Driver with wiring.
Abbildung 3.1: The Fulham FHS2-UNV-36L Emergency LED Driver (right) shown with its associated wiring. This image illustrates the compact form factor and the various wire connections required for installation, including connections to an external battery pack (left, FHSBATL6-3) and the LED load.

4. Einrichtung und Installation

Installation must be performed by a qualified electrician in compliance with all national and local electrical codes. Ensure power is disconnected before beginning any installation work.

4.1 Verdrahtungsanweisungen

  1. Stromabschaltung: Turn off the main power supply to the circuit where the emergency driver will be installed. Verify power is off using a voltage Tester.
  2. Montage: Mount the FHS2-UNV-36L emergency driver securely within the fixture or in an accessible location, ensuring proper ventilation. The unit has a rectangular aluminum housing.
  3. AC-Eingangsanschluss: Connect the AC input wires of the emergency driver to the unswitched AC power supply (100-277V). Typically, this involves connecting the black wire to Line, white wire to Neutral, and green wire to Ground.
  4. Batterieanschluss: Connect the emergency driver to a compatible external battery backup unit (e.g., Fulham FHSBATL6-3, if applicable). Ensure correct polarity (positive to positive, negative to negative). The product description states the battery backup is not included with the FHS2-UNV-36L.
  5. LED Load Connection: Connect the output wires of the emergency driver to the LED load. Observe correct polarity for the LED module. The output voltagDer Bereich beträgt 11–36 V DC.
  6. Test Switch/Indicator: If applicable, connect the test switch and charge indicator light according to the wiring diagram provided with the battery backup unit. This allows for manual testing of the emergency function.
  7. Wiederherstellung der Stromversorgung: Once all connections are secure and verified, restore power to the circuit. The charge indicator light should illuminate, indicating the battery is charging.

Note: Always refer to the specific wiring diagram provided with your complete emergency lighting system for detailed connection instructions.

5. Bedienungsanleitung

The Fulham FHS2-UNV-36L Emergency LED Driver operates automatically. No user intervention is required during normal operation or during a power outage.

  • Normalmodus: When AC power is present, the emergency driver's battery unit (if connected) will charge. The LED luminaire operates normally, powered by the standard AC supply.
  • Notfallmodus: Upon interruption of normal AC power, the emergency driver automatically switches to emergency mode. It draws power from the connected battery backup unit and supplies power to the LED load, illuminating the fixture for a minimum of 90 minutes.
  • Zurück zur Normalität: When AC power is restored, the emergency driver automatically returns to normal mode, and the battery unit begins recharging.

5.1 Testing Emergency Function

Regular testing is crucial to ensure the emergency lighting system is functioning correctly.

  1. Monatlicher Test: Press the test switch (if installed) for at least 30 seconds. The LED luminaire should operate in emergency mode. Release the switch; the luminaire should return to normal operation.
  2. Jährlicher Test: Conduct a full 90-minute discharge test annually. Disconnect AC power to the emergency driver for 90 minutes. The LED luminaire should remain illuminated for the entire duration. After the test, restore AC power and allow the battery to fully recharge (typically 24 hours).

6. Wartung

The Fulham FHS2-UNV-36L Emergency LED Driver is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance.

  • Reinigung: Halten Sie das Gerät sauber und frei von Staub und Schmutz. Verwenden Sie zum Reinigen ein trockenes, weiches Tuch. Verwenden Sie keine flüssigen Reinigungsmittel.
  • Inspektion: Periodically inspect the wiring for any signs of damage, loose connections, or corrosion.
  • Batteriewechsel: The lifespan of the external battery backup unit varies. If the unit fails to maintain illumination for the full 90-minute duration during an annual test, the battery may need replacement. Refer to the battery manufacturer's instructions for replacement procedures.

7. Fehlerbehebung

If the emergency LED driver is not functioning as expected, refer to the following troubleshooting guide:

ProblemMögliche UrsacheLösung
LED luminaire does not illuminate in emergency mode.No AC power to the emergency driver.
Battery not charged or faulty.
Falsche Verkabelung.
Defekte LED-Last.
Überprüfen Sie den Sicherungsautomaten und die Verdrahtungsanschlüsse.
Allow 24 hours for battery to charge. If problem persists, replace battery.
Verify all wiring connections according to the diagram.
Testen Sie die LED-Last mit einer als funktionierend bekannten Stromquelle.
Emergency illumination duration is less than 90 minutes.Batterie nicht vollständig geladen.
Die Batterie nähert sich dem Ende ihrer Lebensdauer.
Incompatible LED load.
Ensure battery has had sufficient time to charge (24 hours).
Replace the battery backup unit.
Verify LED load specifications are within the driver's output range.
Die Ladeanzeigeleuchte ist aus.No AC power to the emergency driver.
Faulty indicator light or wiring.
Batterie nicht angeschlossen.
Überprüfen Sie die Wechselstromversorgung.
Inspect indicator light and its connections.
Stellen Sie sicher, dass die Batterie ordnungsgemäß angeschlossen ist.

If troubleshooting steps do not resolve the issue, contact Fulham customer support or a qualified electrician.

8. Spezifikationen

BesonderheitSpezifikation
ModellnummerFHS2-UNV-36L
Eingangslautstärketage100-277V AC
Ausgangsvolumentage11-36V DC
Maximale Ausgangsleistung20 Watt
AmpAlter0.07 Amps
NotbetriebszeitMindestens 90 Minuten
Abmessungen (L x B x H)10.25" x 1.5" x 1.25" (26.04 cm x 3.81 cm x 3.18 cm)
Gewicht9.9 Unzen (0.28 kg)
MaterialAluminium
MontagetypGestellmontage
Batterie im Lieferumfang enthaltenNEIN
UPC847098011026

9. Garantie und Support

Fulham products are manufactured to high-quality standards and are backed by a manufacturer's warranty. For specific warranty terms and conditions, please refer to the warranty statement provided with your purchase or visit the official Fulham website. For technical support, troubleshooting assistance, or to inquire about replacement parts, please contact Fulham customer service.

Fulham Contact Information:
Besuchen Sie www.fulham.com Für die aktuellsten Kontaktdaten und Support-Ressourcen.

© 2023 Fulham. All rights reserved. Information subject to change without notice.

Ask a question about this manual