1. Einleitung
This manual provides essential instructions for the installation, operation, maintenance, and troubleshooting of your APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI). This Uninterruptible Power Supply (UPS) is designed to provide high-density, true double-conversion online power protection for critical electronic equipment, including servers, voice/data networks, medical labs, and light industrial applications. Please read this manual thoroughly before installing or operating the UPS to ensure proper and safe usage.
2. Sicherheitshinweise
Observe all warnings and operating instructions in this manual. Failure to do so may result in injury or equipment damage. This UPS contains hazardous voltages. Do not attempt to disassemble the unit. There are no user-serviceable parts inside.
Allgemeine Sicherheit
- Diese USV ist nur für den Einsatz in Innenräumen vorgesehen.
- Betreiben Sie diese USV nicht in direktem Sonnenlicht, in Kontakt mit Flüssigkeiten oder an Orten mit übermäßiger Staub- oder Feuchtigkeitsbelastung.
- Ensure the ventilation openings on the UPS are not blocked. Maintain adequate clearance around the unit for proper airflow.
- Connect the UPS power cable directly to a grounded wall outlet. Do not use extension cords or surge suppressors.
Batteriesicherheit
- Batteries are heavy. Remove the battery module before installing the UPS in a rack or tower configuration.
- Battery service should be performed or supervised by personnel knowledgeable of batteries and the required precautions.
- Werfen Sie Batterien nicht ins Feuer. Die Batterien könnten explodieren.
- Batterien dürfen nicht geöffnet oder beschädigt werden. Austretender Elektrolyt ist schädlich für Haut und Augen. Er kann giftig sein.
- Replace batteries with the same type and number of batteries as originally installed.
3. Packungsinhalt
Carefully unpack the unit and inspect for shipping damage. If any damage is found, notify the carrier and dealer. The package should contain the following items:
- APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI) unit
- Battery module (may be pre-installed or separate)
- Rack-mounting hardware (rails, brackets)
- Tower stand (for tower configuration)
- USB-Kommunikationskabel
- Serielles Kommunikationskabel
- Dokumentations-CD
- Safety information and warranty guide
4. Produktüberschreitungview
The APC Smart-UPS SRT 3000VA RM 230V is a high-performance Uninterruptible Power Supply designed to protect your critical equipment from power disturbances. It features a rack/tower convertible form factor for flexible deployment.

Abbildung 1: Vorderseite view of the APC Smart-UPS SRT 3000VA RM 230V. This image displays the front panel with the LCD display, control buttons, and ventilation grilles.
Schlüsselkomponenten
- Front Panel LCD Display: Provides real-time status information, configuration options, and alarm notifications.
- Bedientasten: Used to navigate the LCD menu, power on/off the UPS, and perform self-tests.
- Batteriemodul: Provides backup power during outages. Hot-swappable for easy replacement.
- Eingangsstromanschluss: Connects the UPS to the utility power source.
- Output Receptacles (IEC 320): Provide protected power to connected equipment.
- Communication Ports (USB, Serial): For connecting to a computer or network management card for monitoring and control.
- EPO-Port (Notabschaltung): Allows for remote emergency shutdown of the UPS.
5. Einrichtung
Follow these steps for initial setup of your UPS.
Schritt 1: Wählen Sie einen Standort
- Place the UPS on a sturdy, level surface or install it in a standard 19-inch rack.
- Ensure the ambient temperature is between 0°C and 40°C (32°F and 104°F).
- Maintain at least 10 cm (4 inches) of clearance at the front and rear of the unit for proper ventilation.
Step 2: Install the Battery Module
If the battery module is not pre-installed, slide it into the battery bay until it clicks into place. Connect the battery cables as indicated by the labels.
Step 3: Connect to Utility Power
- Schließen Sie das Eingangsnetzkabel der USV an eine geerdete 230V-Wechselstromsteckdose an.
- The UPS will perform a self-test and the LCD display will illuminate.
Schritt 4: Geräte anschließen
- Connect your critical equipment (servers, network devices, etc.) to the output receptacles on the rear of the UPS.
- Ensure the total load does not exceed the UPS capacity (3000VA / 2700W).
Step 5: Connect Communication Cables (Optional)
- Schließen Sie das USB- oder serielle Kabel der USV an Ihren Computer oder Server an, um Überwachungs- und kontrollierte Herunterfahrfunktionen zu nutzen.
- Install the PowerChute software (available from APC website) on your computer for advanced management.
6. Betrieb der USV
Einschalten der USV
Press and hold the power button on the front panel until you hear a beep. The UPS will start up and provide power to connected equipment.
Powering Off the UPS
Press and hold the power button until the UPS shuts down. Ensure all connected equipment is safely shut down before powering off the UPS.
LCD-Display und Navigation
The LCD display provides detailed information about the UPS status, battery charge, load level, and various settings. Use the navigation buttons (up, down, enter, escape) to browse through the menus and adjust settings.
Selbsttest
Regularly perform a self-test to ensure the UPS battery and internal components are functioning correctly. This can typically be initiated via the LCD menu or PowerChute software.
7. Wartung
Batteriewechsel
The UPS batteries have a typical lifespan of 3-5 years. The UPS will indicate when the batteries need replacement. Refer to the safety information before attempting battery replacement. Use only APC-approved replacement battery modules (APCRBC152).
Reinigung
Reinigen Sie die Außenseite der USV mit einem weichen, fusselfreien Tuch.amp cloth. Do not use solvents or abrasive cleaners. Ensure ventilation openings are free from dust and debris.
Umweltaspekte
Store the UPS in a cool, dry place when not in use. Avoid extreme temperatures and humidity, which can shorten battery life.
8. Fehlerbehebung
Dieser Abschnitt bietet Lösungen für häufig auftretende Probleme mit Ihrer USV.
| Problem | Mögliche Ursache | Lösung |
|---|---|---|
| Die USV schaltet sich nicht ein. | No utility power; Battery not connected; UPS fault | Check power outlet; Ensure battery cables are connected; Contact APC support if fault persists. |
| Die USV piept ununterbrochen. | On battery power; Overload; Low battery | Check utility power; Reduce connected load; Allow battery to recharge. |
| Akku wird nicht geladen | Battery disconnected; Battery fault; Internal fault | Verify battery connection; Replace battery if faulty; Contact APC support. |
| Angeschlossene Geräte verlieren Strom | UPS overload; Battery depleted; UPS fault | Reduce load; Allow battery to recharge; Contact APC support. |
9. Spezifikationen
Detailed technical specifications for the APC Smart-UPS SRT 3000VA RM 230V (SRT3000RMXLI).
| Besonderheit | Detail |
|---|---|
| Modellnummer | SRT3000RMXLI |
| Marke | APC |
| Kapazität | 3000 VA / 2700 Watt |
| Eingangslautstärketage | 230 Volt |
| Ausgangsvolumentage | 230 Volt |
| Formfaktor | Rack/Tower Convertible (2U) |
| Akku-Typ | Bleisäure |
| Typische Laufzeit (Volllast) | Ungefähr 4 Minuten |
| Anzahl der Verkaufsstellen | 8 x IEC 320 C13, 2 x IEC 320 C19 |
| Kommunikationsanschlüsse | USB, Serial (RJ45), SmartSlot |
| Abmessungen (H x B x T) | 8.5 cm x 43.2 cm x 63.5 cm (3.35 Zoll x 17.0 Zoll x 25.0 Zoll) |
| Gewicht | 31.3 kg |
| Farbe | Schwarz |
10. Garantie und Support
Garantieinformationen
APC provides a standard warranty for this product. Please refer to the warranty card included in your package or visit the official APC webAuf der Website finden Sie die detaillierten Garantiebedingungen für Ihre Region. Bewahren Sie Ihren Kaufbeleg für Garantieansprüche auf.
Technische Unterstützung
For technical assistance, troubleshooting beyond this manual, or to inquire about replacement parts, please contact APC customer support. Support contact information can typically be found on the APC website or in the documentation provided with your unit. When contacting support, please have your model number (SRT3000RMXLI) and serial number ready.