1. Zu Endeview
The KYORITSU AC Clamp Meter 2002PA is a versatile electrical measuring instrument designed for accurate measurement of AC current up to 2000A. It features a large teardrop-shaped core for easy clamping around conductors, a recorder output terminal, and multiple functions including AC/DC voltage, resistance, and continuity testing. This manual provides essential information for safe and effective use of the device.

Figure 1: KYORITSU AC Clamp Meter 2002PA
This image shows the KYORITSU AC Clamp Meter 2002PA, a black handheld device with a red clamp jaw at the top. The display shows "000" and there are several buttons below it. The device is designed for measuring electrical current without direct contact.
2. Sicherheitshinweise
Always read and understand this instruction manual before using the KYORITSU AC Clamp Meter 2002PA. Failure to follow safety instructions may result in electric shock, fire, or damage to the device. This product complies with IEC 61010-1, IEC 61010-031, IEC 61010-2-032, and IEC 61326-1 standards.
- Nicht use the meter if it appears damaged or is operating abnormally.
- Nicht anwenden voltage or current exceeding the maximum rated values.
- Vor dem Betrieb sicherstellen, dass der Batteriedeckel fest verschlossen ist.
- Always wear appropriate personal protective equipment (PPE) when working with electrical circuits.
- Nicht use the meter in wet environments or during electrical storms.
- Refer to local and national safety codes for proper electrical work procedures.
3. Hauptmerkmale
- Large Teardrop Core: Facilitates easy clamping around thick conductors.
- Hochstrommessung: Capable of measuring large AC currents up to 2000A.
- Multifunktional: Measures AC current, AC voltage, DC-Voltage, Widerstand und Kontinuität.
- Recorder Output Terminal: Allows connection to external recording devices.
- Hohe Auflösung: Features a small resolution of 0.1A for precise measurements.
- Data Hold & Peak Hold: For capturing stable or peak readings.
- Automatische Energiesparfunktion: Extends battery life by automatically turning off after a period of inactivity.
4. Einrichtung
4.1 Einlegen der Batterie
- Suchen Sie den Batteriefachdeckel auf der Rückseite des Messgeräts.
- Use a screwdriver (if required) to open the battery compartment.
- Insert two AA (R6P, 1.5V) batteries, ensuring correct polarity.
- Bringen Sie die Abdeckung des Batteriefachs wieder an und befestigen Sie sie fest.
4.2 Connecting Test Leads (for Voltage/Widerstand/Kontinuität)
- Insert the red test lead into the VΩ terminal.
- Stecken Sie die schwarze Messleitung in den COM-Anschluss.
- Vor der Messung sicherstellen, dass die Verbindungen sicher sind.
5. Bedienungsanleitung
5.1 Messung von Wechselstrom
- Turn the rotary switch to the "ACA" position.
- Öffne dieamp Kiefer durch Drücken des Hebels.
- Schließen Sie nur einen Leiter des zu messenden Stromkreises in die Klemme ein.amp Kiefer.
- Release the lever to close the clamp jaw securely around the conductor.
- Lesen Sie den auf dem LCD-Display angezeigten Wechselstromwert ab.
5.2 Messen der Wechselspannungtage
- Turn the rotary switch to the "ACV" position.
- Connect the test leads across the circuit points where voltage soll gemessen werden.
- Lesen Sie den AC-BandtagDer auf dem LCD angezeigte Wert.
5.3 Messen der Gleichspannungtage
- Turn the rotary switch to the "DCV" position.
- Connect the test leads across the circuit points where voltage is to be measured, observing polarity.
- Lesen Sie den DC-BandtagDer auf dem LCD angezeigte Wert.
5.4 Widerstandsmessung
- Drehen Sie den Drehschalter auf die Position "Ω".
- Vor der Widerstandsmessung muss sichergestellt werden, dass der Stromkreis spannungsfrei ist.
- Connect the test leads across the component or circuit path to be measured.
- Read the resistance value displayed on the LCD.
5.5 Durchgangstest
- Turn the rotary switch to the "Continuity" position (often indicated by a speaker icon).
- Stellen Sie sicher, dass der Stromkreis spannungsfrei ist.
- Verbinden Sie die Messleitungen mit dem Bauteil oder dem Stromkreis.
- If continuity exists (resistance below approximately 50±35Ω), the buzzer will sound.
6. Wartung
6.1 Reinigung
- Wipe the meter with a soft, dry cloth.
- Nicht Scheuermittel oder Lösungsmittel verwenden.
6.2 Batteriewechsel
- When the battery indicator appears on the display, replace the batteries as described in Section 4.1.
- Um ein Auslaufen zu verhindern, entfernen Sie die Batterien, wenn das Messgerät längere Zeit nicht benutzt wird.
7. Fehlerbehebung
| Problem | Mögliche Ursache | Lösung |
|---|---|---|
| Keine oder nur schwache Anzeige | Niedrige Batteriespannung oder falsche Batterieeinlegung. | Batterien austauschen oder Polarität prüfen. |
| Ungenaue Messwerte | Incorrect function selected, poor test lead contact, or external magnetic fields. | Verify function, ensure good contact, move away from strong magnetic sources. |
| Kein Durchgangssignal | Circuit is open, or resistance is too high. | Check circuit for breaks, ensure circuit is de-energized. |
8. Spezifikationen

Figure 2: Detailed specifications for KYORITSU AC Clamp Meter 2002PA and 2002R (RMS).
This image displays a table of detailed specifications for the KYORITSU AC Clamp Meter models 2002PA and 2002R. It includes measurement ranges and accuracies for AC current, AC voltage, DC-Voltage, resistance, and continuity, along with physical dimensions, power source, and compliance standards.
| Parameter | Specification (Model 2002PA) |
|---|---|
| Wechselstrom (50/60 Hz) | 400.0/2000A ±1%rdg±3dgt (0-400A) ±1%rdg±3dgt (0-1500A) ±3%rdg (1501-2000A) |
| AC Current (40Hz-1kHz) | ±2%rdg±3dgt (0-400A) ±3%rdg±3dgt (0-1500A) |
| AC-Lautstärketage | 40.00/400.0/750 V ±1 % v.M. ±2 dgt (50/60 Hz) ±1.5%rdg±3dgt (40Hz-1kHz) |
| DC-Voltage | 40.00/400.0/1000 V ± 1% rdg ± 2dgt |
| Widerstand | 400.0Ω/4.000/40.00/400.0kΩ ± 1.5% rdg ± 2dgt |
| Kontinuität | 400.0Ω (Buzzer sounds below 50±35Ω) |
| Scheitelfaktor | 3 or less (Accuracy +1% for 45-65Hz) Peak value AC3000A/1200V or less |
| Max. Measurable Conductor Diameter | Ø55 mm |
| Ausgabe | Recorder output: DC400mV for AC400A, DC200mV for AC2000A |
| Compliance-Standards | IEC 61010-1 (JIS C 1010-1) CAT.III 600V, CAT.II 1000V IEC 61010-031 (JIS C 1010-31) IEC 61010-2-032 (JIS C 1010-2-32) Norm IEC 61326-1 |
| Stromquelle | 2 x AA batteries (R6P, 1.5V) |
| Dauergebrauchszeit | Approx. 150 hours (Auto power save approx. 10 min) |
| Abmessungen (L x B x T) | 247 x 105 x 49 mm |
| Gewicht | Ca. 470g (inkl. Batterien) |
| Mitgeliefertes Zubehör | Test leads (7107A), Output plug (8201), Carrying case (9094), 2 x AA batteries (R6P), Instruction manual |
| Optionales Zubehör | Multi-trans (8008) |
9. Garantie und Support
For warranty information, technical support, or service inquiries, please refer to the contact details provided in the product packaging or visit the official KYORITSU webBewahren Sie Ihren Kaufbeleg als Kaufnachweis für Garantieansprüche auf.