1. Zu Endeview
The Gentex GX93 Series mini-horn is a remote signaling appliance designed for dependable annunciation in supervised fire protective systems. It is suitable for use with both filtered and unfiltered power sources and meets NFPA and other relevant code requirements. The GX93 Series offers field-selectable 12VDC or 24VDC operation, providing flexibility for various system configurations. It can produce either a temporal or continuous tone.
Zu den Hauptmerkmalen gehören:
- Vor Ort wählbare Lautstärketage: Operates on 12VDC or 24VDC, accommodating regulated and non-regulated power sources.
- Tone Options: Provides temporal or continuous tone output.
- Verdrahtungskompatibilität: Terminal blocks support 12 AWG to 18 AWG wires.
- Langlebige Konstruktion: Features a textured high-impact plastic faceplate.
- Unterputzmontage: Designed for unobtrusive installation on walls or ceilings.
- Synchronisierungsfunktion: Can be synchronized with other GX93 Series horns using a Gentex Synchronization Module (e.g., GX91/GX93).
- Zertifizierungen: UL/ULC dual listed, ensuring compliance with fire safety standards.

Figure 1: Gentex GX93 Series Mini-Horns. An image showing two Gentex GX93 Series mini-horns. The one on the left is off-white, and the one on the right is a darker color, likely red or gray. Both units feature a rectangular design with vertical grilles for sound output and a small indicator light at the bottom.
2. Sicherheitshinweise
Read all instructions carefully before installation and operation. Failure to follow these instructions may result in property damage, serious injury, or death.
- Installation must be performed by qualified personnel in accordance with all national and local codes and standards, including NFPA 72.
- Disconnect all power to the fire alarm control panel (FACP) or power supply before wiring.
- Ensure proper polarity when connecting wiring to avoid damage to the device.
- Do not paint over the device, as this may impair its functionality.
- Test the device regularly as part of a comprehensive fire alarm system maintenance plan.
- Dieses Gerät ist nur für den Gebrauch in Innenräumen vorgesehen.
3. Einrichtung und Installation
3.1 Montage
The GX93-W mini-horn is designed for flush mounting on walls or ceilings. Ensure the mounting location is clean, dry, and free from obstructions. The device should be mounted in accordance with local building codes and NFPA 72 requirements for audible signaling devices.
- Wählen Sie einen geeigneten Montageort an der Wand oder Decke.
- Prepare the electrical box or mounting surface according to standard practices.
- Secure the device's mounting plate (if applicable) to the electrical box or surface.
- Ensure the device is securely fastened and flush with the mounting surface.
3.2 Verkabelung
Wiring must be performed with power disconnected from the FACP. The GX93-W supports 12 AWG to 18 AWG wires. Observe proper polarity.
- Connect the positive (+) wire from the FACP or power supply to the positive terminal on the GX93-W.
- Connect the negative (-) wire from the FACP or power supply to the negative terminal on the GX93-W.
- If using a synchronization module (e.g., Gentex GX91/GX93), refer to the synchronization module's manual for specific wiring instructions.
- Stellen Sie sicher, dass alle Verbindungen sicher und ordnungsgemäß isoliert sind.
3.3 Voltage and Tone Selection
The GX93-W allows for field selection of operating voltage (12VDC or 24VDC) and tone type (temporal or continuous). Consult the device's internal jumpers or switches for configuration. Refer to the markings on the device for specific settings.
4. Bedienung
The Gentex GX93-W mini-horn functions as an audible signaling device within a supervised fire alarm system. When activated by the FACP, it will emit an audible tone according to its configured settings (temporal or continuous).
- Temporal 3 Tone: This is a specific pattern of three short bursts followed by a pause, commonly used for fire evacuation signals. Note that the sound output rating for temporal 3 tone is averaged, meaning the peak sound pressure during the tone burst is higher than the stated average.
- Continuous Tone: A steady, uninterrupted audible signal.
- Synchronisation: If connected to a compatible synchronization module, multiple GX93 Series horns will activate in a synchronized pattern.
5. Wartung
Regular maintenance ensures the continued reliable operation of your GX93-W mini-horn.
- Reinigung: Periodically clean the exterior of the device with a soft, dry cloth to remove dust and debris. Do not use abrasive cleaners or solvents.
- Testen: The mini-horn should be tested regularly as part of the overall fire alarm system testing protocol, as required by NFPA 72 and local authorities.
- Inspektion: Visually inspect the device for any signs of damage, discoloration, or loose connections.
- Nicht zerlegen: Versuchen Sie nicht, das Gerät zu zerlegen oder zu reparieren. Überlassen Sie alle Wartungsarbeiten qualifiziertem Fachpersonal.
6. Fehlerbehebung
If the GX93-W mini-horn is not functioning as expected, consider the following:
- Kein Ton:
- Check power supply to the FACP and the device.
- Verify wiring connections for proper polarity and secure contact.
- Ensure the FACP is activating the signaling circuit.
- Korrekte Lautstärke bestätigentage selection (12VDC or 24VDC) matches the power supply.
- Falscher Ton:
- Verify the tone selection settings (temporal or continuous) on the device.
- If using a synchronization module, ensure it is correctly configured and functioning.
- Intermittierender Betrieb:
- Überprüfen Sie die Verkabelung auf lose Verbindungen oder beschädigte Isolierung.
- Überprüfen Sie die Lautstärketage fluctuations from the power source.
If issues persist after troubleshooting, contact qualified fire alarm service personnel.
7. Spezifikationen
| Attribut | Wert |
|---|---|
| Modellnummer | GX93W |
| Marke | Gentex |
| Betriebslautstärketage | 12VDC or 24VDC (Field Selectable) |
| Tonart | Temporal 3 or Continuous (Field Selectable) |
| Verkabelungskompatibilität | 12 AWG bis 18 AWG |
| Montagetyp | Flush Wall Mount, Flush Ceiling Mount |
| Technische Daten | 3 x 3 x 1.5 Zoll (ungefähr) |
| Artikelgewicht | 3.2 Unzen (ungefähr) |
| Farbe | Cremefarben |
| Zertifizierungen | UL/ULC Listed (UL 464) |
| UPC | 700217022856 |
8. Garantie und Support
8.1 Garantieinformationen
The Gentex GX93-W mini-horn is warranted for drei Jahre from the date of purchase against defects in materials and workmanship under normal use. This warranty does not cover damage caused by improper installation, misuse, abuse, or unauthorized modifications.
8.2 Technischer Support
For technical assistance, installation questions, or warranty claims, please contact Gentex customer support or your authorized Gentex distributor. Please have your model number (GX93W) and date of purchase available when contacting support.