Uponor 1022244

Uponor Thermal Actuator 230V NC M28 x 1.5 Instruction Manual

Modell: 1022244

1. Produktüberschreitungview

The Uponor Thermal Actuator (Model 1022244) is designed for precise control of valves in Uponor, Polytherm, and Wirsbo Vario B underfloor heating distributors. This actuator operates on 230V AC and features a Normally Closed (NC) function, meaning the valve is closed when no power is supplied and opens when power is applied.

Zu den Hauptmerkmalen gehören:

Uponor Thermal Actuator 1022244

Figure 1: Uponor Thermal Actuator (Model 1022244). This image shows the blue housing and grey base of the actuator.

2. Sicherheitshinweise

Please read all safety instructions carefully before installation and operation. Failure to follow these instructions may result in electric shock, fire, or property damage.

3. Installation und Einrichtung

This section provides instructions for the correct installation of the thermal actuator onto your underfloor heating manifold.

  1. Ausschalten: Ensure the main power supply to the underfloor heating system is completely disconnected at the circuit breaker.
  2. Identify Valve: Locate the specific valve on the Uponor, Polytherm, or Wirsbo Vario B underfloor heating distributor where the actuator is to be installed.
  3. Mount Actuator: Carefully screw the thermal actuator onto the valve's M28 x 1.5 internal thread. Hand-tighten until secure. Do not overtighten.
  4. Elektrischer Anschluss: Connect the 230V AC electrical cable from the actuator to the appropriate control terminal on your heating system's wiring center. Ensure connections are secure and comply with local electrical codes. The actuator functions as Normally Closed (NC), meaning it will open the valve when power is supplied.
  5. Verify Indicator: After connection, the lift indicator on the actuator should be visible. Its position will change once power is applied and the actuator begins to operate.
  6. Strom wiederherstellen: Once all connections are secure and verified, restore power to the heating system.
Uponor Thermal Actuator with cable diagram

Figure 2: Diagram of the Uponor Thermal Actuator showing its connection cable. This illustrates the electrical connection point.

4. Bedienung

The Uponor Thermal Actuator operates based on the electrical signal it receives from the heating control system.

5. Wartung

The Uponor Thermal Actuator is designed for long-term, maintenance-free operation. However, periodic visual inspections are recommended.

No internal maintenance or lubrication is required for this device.

6. Fehlerbehebung

If you experience issues with your Uponor Thermal Actuator, consult the following troubleshooting guide:

ProblemMögliche UrsacheLösung
Actuator not opening/closingNo power supply to the actuator.
Fehlerhafte Verdrahtung.
Aktuatorausfall.
Check if 230V AC is supplied to the actuator when heat is demanded.
Stellen Sie sicher, dass alle elektrischen Verbindungen sicher sind.
If power is present and connections are good, the actuator may need replacement.
Lift indicator not movingKein Strom oder unzureichender Strom.
Mechanische Blockade.
Confirm 230V AC power supply.
Ensure the actuator is correctly seated on the valve and there are no obstructions.
Water leakage around valveActuator not properly tightened.
Faulty valve or manifold.
Ensure the actuator is securely hand-tightened onto the valve. Do not use tools to overtighten.
Inspect the valve and manifold for damage. Contact a qualified plumber if the leak persists.

If troubleshooting steps do not resolve the issue, contact a qualified technician or Uponor customer support.

7. Technische Daten

Detailed specifications for the Uponor Thermal Actuator (Model 1022244).

Uponor Thermal Actuator dimensional drawing

Figure 3: Dimensional drawing of the Uponor Thermal Actuator. This diagram provides key measurements for installation planning.

SpezifikationWert
HerstellerUponor
Modellnummer1022244
Nennvolumentage230 V Wechselspannung
max. Derzeitiger Verbrauch0.14 A
Max. Stromverbrauch2 Watt
FunktionNormalerweise geschlossen (NC)
Interner ThreadM28 x 1.5
Verbindungskabel0.75 mm² x 1 m
Abmessungen (L x B x H)7.5 x 5 x 5 cm
Gewicht120 Gramm
FarbeBlau

8. Garantie und Support

For warranty information, technical support, or spare parts availability, please contact Uponor customer service or your local distributor. Keep your purchase receipt as proof of purchase.

Uponor GmbH Contact Information:

Industriestraße 56
97437 Haßfurt
Deutschland
Telefon: +492221090866
E-Mail: Kundenservice@uponor.com
WebWebsite: www.uponor.com/de-de

Zugehörige Dokumente - 1022244

Vorview Uponor Vario / Vario PLUS Stellantrieb Installations- und technisches Handbuch
Ausführlicher Leitfaden zu den Uponor Vario und Vario PLUS Stellantrieben, der Installation, Bedienung, Funktionen wie „First-Open“ und detaillierte technische Spezifikationen für HLK-Systeme abdeckt.
Vorview Uponor Vario Nachrüst-Stellantrieb: Installationsanleitung und technische Spezifikationen
Ausführlicher Leitfaden zur Installation und zum Betrieb des Uponor Vario Nachrüstantriebs, einschließlich detaillierter technischer Spezifikationen, Kompatibilitätsinformationen und Sicherheitshinweisen für HLK-Systeme.
Vorview Uponor Quik Trak® Konstruktions- und Installationshandbuch
Ausführlicher Leitfaden für die Planung und Installation des Uponor Quik Trak Flächenheizungssystems mit detaillierten Installationsmethoden für verschiedene Untergründe, Wandanwendungen, Berechnungen und Systemdesign.
Vorview Uponor Fußbodenheizung und -kühlung: Planungsleitfaden
Dieser umfassende Planungsleitfaden von Uponor beschreibt detailliert Fußbodenheizungs- und -kühlsysteme und behandelt technische Spezifikationen, Designkriterien, Installationsverfahren und den hydraulischen Abgleich für optimale Klimatisierungslösungen.
Vorview Uponor PEX Referenzhandbuch für gewerbliche Rohrleitungssysteme
Ein umfassendes Nachschlagewerk für Architekten, Ingenieure und Bauunternehmer zu Uponor PEX- und ProPEX-Fittings für gewerbliche Sanitär- und Hydronik-Rohrleitungssysteme. Umfasst technische Spezifikationen, Leistungsdaten, Installationsrichtlinien, Vorschriften und Normen.
Vorview Uponor Classic Installationshandbuch
Dieses Handbuch enthält detaillierte Installationsanweisungen für das Uponor Classic System, einschließlich Rohrverlegung, Verteileranschluss und Druckprüfung. Es behandelt die wichtigsten Schritte für eine erfolgreiche und effiziente Installation des Uponor Classic Fußbodenheizungssystems.