Elitech DMG-4B

Elitech Smart Digital Manometer DMG-4B Benutzerhandbuch

Model: DMG-4B

Marke: Elitech

1. Produktüberschreitungview

The Elitech Smart Digital Manifold Gauge DMG-4B is designed to provide precise measurements for HVAC/R systems. It offers advanced features such as remote firmware upgrades, a comprehensive refrigerant database, and smart app control via Bluetooth. This device aims to simplify complex refrigeration tasks with its digital accuracy and robust design.

Elitech Smart Digital Manifold Gauge DMG-4B

Image: Elitech Smart Digital Manifold Gauge DMG-4B, front view.

Zu den Hauptmerkmalen gehören:

  • Remote firmware upgrade (OTA) for up-to-date functionality.
  • Supports over 140 types of refrigerants with instant updates via the Elitech Tools APP.
  • Bluetooth connectivity for real-time data monitoring and analysis.
  • Digital sensors for enhanced measurement accuracy.
  • Compact, portable, and durable design with up to 200 hours of battery life.

2. Lieferumfang

The Elitech Smart Digital Manifold Gauge DMG-4B package includes the following items:

  • 1 x Digital Manifold Gauge (DMG-4B)
  • 1 x Tragetasche
  • 1 x Benutzerhandbuch
  • 1 x Verpackungsbox
Elitech DMG-4B Packing List

Image: Contents of the Elitech DMG-4B package, including the manifold, bag, and manual.

3. Einrichtungsanweisungen

Follow these steps to set up your Elitech Smart Digital Manifold Gauge DMG-4B for initial use.

3.1. Initial Calibration and Refrigerant Selection

Before each measurement, it is crucial to calibrate the pressure sensor and select the correct refrigerant type.

  1. Ensure there is no connection between the gauge and any pressure source. The gauge should be at atmospheric pressure.
  2. Long press the 'Zero' button to calibrate the pressure sensor. The calibration range is 1-100psi.
  3. To switch the refrigerant type, long press 'Zero' and the 'Down Arrow' button together. Then, short press 'Up Arrow' or 'Down Arrow' to cycle through available refrigerant types.

Video: This video demonstrates how to use the Elitech DMG-4B, including initial setup, calibration, and refrigerant selection.

3.2. App Connection and Firmware Upgrade (OTA)

The Elitech Tools app enhances the functionality of your manifold gauge. It also allows for remote firmware upgrades to keep your device up-to-date.

  1. Download and open the 'Elitech Tools' app on your smartphone.
  2. Click the menu icon in the upper left corner of the homepage and log in or register an account.
  3. On the manifold gauge, click the Bluetooth button. The Bluetooth icon on the display will flash.
  4. In the app, click 'Search nearby device' and connect to your DMG-4B.
  5. If a newer firmware version is available, the device will prompt you to upgrade. Confirm to start the OTA upgrade process. Alternatively, you can manually initiate a firmware update from the app's settings.

Video: This video demonstrates connecting the manifold gauge to the Elitech Tools app and performing a firmware upgrade.

4. Bedienungsanleitung

The Elitech DMG-4B offers various functions for comprehensive HVAC/R system analysis. Some advanced functions require in-app purchase.

4.1. DIY Refrigerant List

Customize your refrigerant list by selecting from over 140 available types in the app.

  1. In the Elitech Tools app, click on the refrigerant icon in the upper right corner of the dashboard.
  2. Select the refrigerant types you wish to add or remove from your 'Favorite' list by touching the star icon.
  3. Click the update icon in the upper right corner to save your settings and synchronize with the device.

4.2. Pressure Holding Test (Requires In-App Purchase)

This function allows you to test the pressure integrity of your system.

  1. Connect the high-pressure refrigerant hose to the testing system and close the high-pressure valve.
  2. In the app, navigate to 'Settings' and then 'Hold Pressure Setting'.
  3. Set the charging warning value, decay ratio, enable/disable temperature compensation, and set the pressure-holding time.
  4. On the device, press and hold the 'MODE' and 'Down Arrow' keys simultaneously to enter the pressure-holding test.
  5. Inject gas into the system until the pressure reaches the charging warning value. The device will flash and emit a sound.
  6. Click the 'Down Arrow' button on the device to begin the leak test. The timer will start counting down.
  7. If the pressure remains within the acceptable leak value (calculated based on decay ratio), the test is successful. Otherwise, it indicates a leak.

4.3. Vacuum Measurement (Requires In-App Purchase)

Measure the vacuum level of your system.

  1. Connect the system to the high-pressure side of the manifold and open the high-pressure valve.
  2. Simultaneously press the 'MODE' and 'Down Arrow' buttons twice on the device to enter the vacuum mode.
  3. Connect one end of the refrigerant pipe to the vacuum pump.
  4. Start the vacuum pump and extract pressure from the system. The device will display the vacuum degree and elapsed time.

4.4. Offline Data Logging (Requires In-App Purchase)

Record measurement data directly on the device for later analysis.

  1. In the app, navigate to 'Settings' and then 'Record Function'.
  2. Select the desired recording interval (e.g., 1s, 10s, 1min).
  3. Click 'Start Offline Recording'. The recording icon on the device will light up and flash.
  4. To stop recording, click 'Stop Offline Recording'. The recording icon will turn off.
  5. Zu view or export historical data, click 'Read Device History Data' in the app. Data can be exported in PDF or Excel format.
  6. To clear historical data from the device, click 'Clear Historical Data' in the app.

Video: This video provides an introduction to the Elitech DMG-4B APP's value-added functions, including refrigerant list customization, pressure holding test, vacuum measurement, and offline data logging.

5. Wartung

Proper maintenance ensures the longevity and accuracy of your Elitech DMG-4B.

  • Reinigung: Wischen Sie das Gerät regelmäßig mit einem weichen, fusselfreien Tuch ab.amp Tuch. Vermeiden Sie die Verwendung von scheuernden Reinigern oder Lösungsmitteln, die das Material beschädigen könnten.asing oder Bildschirm.
  • Lagerung: Store the manifold gauge in its provided carrying bag in a dry, cool place when not in use.
  • Batteriewechsel: The device uses replaceable AAA batteries. Replace them promptly when the low battery indicator appears to ensure continuous operation.
  • Sensorpflege: Ensure the pressure ports are free from debris and moisture. Always cap the ports when not connected to a system.

6. Fehlerbehebung

This section addresses common issues you might encounter with your Elitech DMG-4B.

AusgabeMögliche UrsacheLösung
Pressure Holding Test Failure
  • System leakage.
  • Refrigerant pipe connection not tightened.
  • Too small leak decay alarm value settings.
  • Check the system for leaks and repair as necessary.
  • Stellen Sie sicher, dass alle Verbindungen fest angezogen sind.
  • Adjust the leak decay alarm value in the app settings if appropriate for your system.
Screen goes blank or dims immediatelyLow battery or display settings.Replace batteries. Check app settings for display brightness or auto-off timers.
Probleme mit der Bluetooth-VerbindungOut of range, interference, or app/device not paired correctly.Ensure device and phone are within Bluetooth range. Restart both the device and the app. Re-pair the device through the app.
Ungenaue MesswerteSensor not calibrated, dirty ports, or incorrect refrigerant selected.Perform pressure sensor calibration. Clean pressure ports. Verify the correct refrigerant type is selected in the device and app.

7. Spezifikationen

Detailed technical specifications for the Elitech Smart Digital Manifold Gauge DMG-4B.

SpezifikationWert
ModellDMG-4B
Artikelgewicht1.5 Pfund (ca. 680 g)
Technische Daten4.33 x 2.95 x 5.31 Zoll (ca. 11 x 7.4 x 13.5 cm)
Druckbereich-14 bis 800 psi
Genauigkeit±1 % vom Endwert
Auflösung1 psi
Druckeinheitenpsi, kg/cm2, kPa, MPa, bar, inHg
Temperatureinheiten° C / ° F.
Batterien2 AAA-Batterien (im Lieferumfang enthalten)
AkkulaufzeitBis zu 200 Stunden
Elitech DMG-4B Dimensions and Specifications

Image: Visual representation of Elitech DMG-4B dimensions and key specifications.

8. Garantie und Support

Elitech provides comprehensive support for its products.

  • Garantie: The Elitech DMG-4B typically comes with a 1-year warranty from the date of purchase. Please refer to the official Elitech webDie genauen Garantiebedingungen finden Sie auf der Website oder in Ihren Kaufunterlagen.
  • Benutzerhandbuch (PDF): For a detailed PDF version of the user manual, please refer to the official product page or Elitech's support resources. Benutzerhandbuch herunterladen (PDF)
  • Online-Hilfe: For further assistance, technical support, or inquiries, visit the official Elitech webWebsite oder wenden Sie sich an den Kundendienst.